Distribution transformers for Peru

Grid in Peru: 10 / 22.9 kV HV, 380/220 V LV, 60 Hz.

  • HV10 / 22.9 kV
  • LV380/220 V
  • Frequency60 Hz
  • Conformity scheme— (confirmed per order)
  • RegionLatin America

Matching product lines

Other HV ratings on request

LV to the destination grid on request

Specifying a distribution transformer for Peru

Peru runs at 60 Hz with 380/220 V recommended for public low-voltage networks. Medium voltage varies by utility (10, 13.2 and 22.9 kV all appear in utility documents), so the voltage, the altitude and the loss tables all need to be fixed in the enquiry.

Medium voltage in use

SourceMedium voltage
State-owned distribution companies (FONAFE group) – transformer specification, 201710, 10.5, 13.2, 13.8, 19.07 and 22.9 kV; dual-primary units 10–22.9, 10–33 and 22.9–33 kV
Luz del Sur (Lima) – connection-cost schedule10 kV, 13.2/7.62 kV and 20 kV–22.9/13.2 kV networks

The FONAFE specification is a 2017 edition published by one of the group’s companies. Confirm with your own utility which of these it uses.

Low voltage and frequency

  • Frequency: 60 Hz nominal (National Electrical Code – Utilisation, rule 020-502).
  • Public low-voltage networks: 380/220 V three-phase four-wire with the neutral effectively earthed is the recommended system; existing voltage levels may continue in use (rule 020-500).
  • The FONAFE transformer specification lists secondaries of 0.40–0.231 kV, 0.46–0.23 kV and 0.231 kV, depending on the item.

Construction details in the FONAFE specification

  • Altitude: designed for 0 to 4500 m above sea level; ambient −15 to 40 °C, relative humidity up to 99 %. The insulation levels are set for the full altitude range.
  • Cooling ONAN or KNAN; winding temperature rise 65 °C; outdoor mounting.
  • Tapping ±2 × 2.5 % on dual-primary units, which must meet the loss tables at both primary voltages.
  • Vector groups in the specification: Dyn5 and Yyn6 (star secondary), Dd6 and Yd7 (delta secondary), depending on the primary voltage and item.
  • Short-circuit impedance 4 % for three-phase units of 15 to 630 kVA.
  • Standards named: IEC 60076-1 and Peruvian NTP 370.400 (distribution transformers: no-load current, losses and short-circuit voltage).
  • Insulation level examples: 10 kV equipment 75 kV impulse; 13.2 kV 95 kV; 22.9 kV 125 kV.

Maximum losses in the specification (three-phase)

Rating≤ 17.5 kV equipment: no-load / load, W17.5–36 kV equipment (includes 22.9 kV): no-load / load, W
100 kVA374 / 1920417 / 1975
250 kVA734 / 3804771 / 3737
400 kVA968 / 55501050 / 5429
630 kVA1411 / 81361486 / 8144

Values from the NTP 370.400 tables as reproduced in the specification; they already include the IEC 60076-1 tolerances. Bidders must state losses as percent of rated power and in watts.

Certification

We did not find a Peruvian regulation that places distribution transformers under mandatory product certification. Tenders from the state-owned distribution companies ask the bidder to state the manufacturing standard (IEC 60076-1, NTP 370.400) and to fill in the guaranteed-data sheet. Ask the utility or your tender documents whether any certificate, test report or approved-manufacturer requirement applies.

What our published ratings cover

  • Oil-immersed S11: published for 6 / 6.3 / 10 / 10.5 / 11 kV (30–4500 kVA) and 20 kV (30–1600 kVA); LV 380, 400, 415 and 433 V; tapping ±2 × 2.5 %; IEC 60076. The published loss values are 50 Hz guarantees. 60 Hz units for Peru are designed and quoted per order.
  • 22.9 kV and 13.2 kV primaries, dual-primary windings, 0.40–0.231 kV and 0.46–0.23 kV secondaries, Dyn5 / Yyn6 / Dd6 / Yd7 vector groups, and the altitude and loss requirements of the specification: on request.
  • Pad-mounted transformers are IEEE/ANSI C57.12 at 60 Hz; their published HV list (up to 19.92 kV) does not include 10 kV or 22.9 kV, and the published LV options do not include 380/220 V, so a Peruvian pad-mounted unit is quoted on request.

Send with your enquiry

  • Utility or project and site (city, altitude in metres above sea level)
  • Rated power (kVA), primary voltage or voltages (10, 13.2, 22.9 kV, or dual), secondary (for example 380/220 V or 400/231 V)
  • Vector group and tapping range; single- or three-phase
  • Loss limits or the standard they come from (for example NTP 370.400), and any guaranteed-data sheet to be filled in
  • Quantity and required delivery date