Distribution transformers for Vietnam

Grid in Vietnam: 22 kV HV, 380 V LV, 50 Hz.

  • HV22 kV
  • LV380 V
  • Frequency50 Hz
  • Conformity scheme— (confirmed per order)
  • RegionSoutheast Asia

Matching product lines

Other HV ratings on request

LV to the destination grid on request

Specifying a distribution transformer for Vietnam

Vietnam’s distribution network runs at 50 Hz, with 22 kV and 35 kV among its nominal medium-voltage levels. The rules that matter to an importer are the nominal voltage levels in the Ministry of Industry and Trade circular, the neutral earthing of each level, and the minimum energy performance requirement for three-phase distribution transformers.

Nominal voltage levels in the distribution system

ItemValue (Circular 05/2025/TT-BCT)
Nominal voltage levels in the distribution system110 kV, 35 kV, 22 kV, 15 kV, 10 kV, 6 kV and 0.38 kV
Medium voltageabove 1 kV up to 35 kV
Low voltageup to 1 kV
Nominal frequency50 Hz, ±0.2 Hz in normal operation

The earlier Circular 39/2015/TT-BCT listed 0.4 kV as the low-voltage level; the current text lists 0.38 kV. Check which figure your utility’s specification uses for the secondary.

Neutral earthing by voltage level

VoltageNeutral point
35 kVisolated or earthed through an impedance
22 kV and 15 kVsolidly earthed (three-phase three-wire) or repeatedly earthed (three-phase four-wire)
10 kV and 6 kVisolated
Below 1,000 Vsolidly earthed

Energy efficiency: labelling and minimum levels

Decision 04/2017/QĐ-TTg lists three-phase distribution transformers among the industrial equipment that must carry an energy label, and it bars the import and production of industrial equipment below the minimum energy performance level (MEPS).

The national standard for that level is TCVN 8525:2015, which gives the minimum efficiency and the method to determine it for three-phase oil-immersed and dry-type distribution transformers up to 4,000 kVA and up to 35 kV, at 50 Hz.

Ask early for test reports to TCVN 8525:2015, since the minimum efficiency applies to imports.

Design standards

Vietnam adopts the IEC 60076 series as TCVN 6306, for example TCVN 6306-1:2015 (IEC 60076-1:2011) and TCVN 6306-11:2009 for dry-type units (IEC 60076-11:2004).

What our published ratings cover

  • YBW compact substations: HV 22 kV and 35 kV are both in the published list (10 / 11 / 20 / 22 / 33 / 35 kV; highest voltage Um 24 and 40.5 kV), 50–2500 kVA, LV 380 / 400 / 415 / 433 V.
  • Oil-immersed S11 / S13: published HV classes are 10 / 11 kV and 20 kV, with LV 380–433 V on the 10 / 11 kV class and 0.4 kV on the 20 kV class (Dyn11). The 20 kV class is the nearest to 22 kV; 22 kV and 35 kV oil-immersed distribution transformers are quoted on request.
  • Power transformers: 35 kV is in the published HV list (33 / 34.5 / 35 / 38.5 kV), 5000–31500 kVA.
  • Dry-type units are published for 6–15 kV; 22 kV dry-type is on request.
  • Test reports to TCVN 8525:2015 and the rated losses for a 22 kV or 35 kV unit: quoted on request. Loss values on this site are listed per rating for the published classes.

Send with your enquiry

  • Electricity company and site (province), and whether the feeder is 22 kV or 35 kV
  • Rated power (kVA), HV and LV (0.4 or 0.38 kV), vector group, tapping range
  • Oil-immersed, dry-type or compact substation; indoor or outdoor; three-phase or single-phase
  • Any utility or project specification, and the efficiency (TCVN 8525) and type-test reports it asks for
  • Quantity, delivery port and required date