Jinying Transformer / Markets / South Africa
Grid in South Africa: 11 / 22 kV HV, 400 V LV, 50 Hz.
400 V is available on this series' low-voltage winding.
South African distribution transformers are bought to SANS 780 and to the owner’s own specification. Eskom and City Power publish theirs, and they differ on details that matter when you order: the no-load secondary voltage, the tapping range and whether the unit must carry the SANS 780 mark.
| Network owner | Medium voltage in its specification |
|---|---|
| Eskom (pole- and ground-mounted, up to 33 kV and 1 MVA) | 11 kV and 22 kV; pole-mounted dual-ratio units switchable between 11 kV and 22 kV; insulation levels also listed for 6.6 kV and 33 kV |
| City Power, Johannesburg (pole-mounted) | 11 kV and 22 kV; 315 kVA units 6.6/11 kV dual ratio |
| City Power, Johannesburg (ground-mounted, up to 1 MVA) | 6.6 kV and/or 11 kV |
Eskom explains the dual-ratio unit as a way to upgrade an 11 kV network to 22 kV without replacing the transformer fleet; the voltage is selected with an external off-load switch on the primary.
SANS 780 is the South African standard for oil-immersed distribution transformers. Edition 5 (2019) replaced the 2009 edition with lower no-load and load losses, and covers single-phase and three-phase units from 16 kVA to 3.15 MVA. It applies to units up to 3,150 kVA with a highest system voltage of 36 kV, with de-energised tapping only, at 50 Hz.
Eskom, municipalities and electrical contractors are the main buyers of units built to it. Eskom’s standard is read together with SANS 780 and takes precedence where the two conflict.
City Power requires every transformer to bear the SANS 780 mark of approval and asks for the SABS permit number in the data schedule. Eskom asks for type-test reports, quality-management certification and mark-scheme permits with the tender, and keeps the right to test production units.
NRCS compulsory specification VC 8055 is written for electrical and electronic apparatus rated up to 600 V and lists small power transformers under SANS 61558. Check with the network owner which approvals it requires for your purchase.