Distribution transformers for Philippines

Grid in Philippines: 13.2 kV HV, 240/480 V LV, 60 Hz.

  • HV13.2 kV
  • LV240/480 V
  • Frequency60 Hz
  • Conformity scheme— (confirmed per order)
  • RegionSoutheast Asia

Matching product lines

Other HV ratings on request

LV to the destination grid on request

Specifying a distribution transformer for the Philippines

The Philippines runs at 60 Hz, and the medium voltage and the secondary system depend on the distribution utility. Meralco, the largest, publishes its service voltages and the transformer types it supplies. Check which utility and which service voltage your site uses before you ask for a quotation.

Frequency and nominal voltages in the Philippine Distribution Code

ItemValue
Frequency60 Hz, allowable variation 59.7–60.3 Hz
Voltage variation at the supply point±10 % of the nominal service voltage
Secondary nominal service voltages230 V, 400 V, 460 V
Primary nominal voltages13.2 kV, 13.8 kV, 34.5 kV, 69 kV, 115 kV

Figures are as quoted by Meralco from the Philippine Distribution Code.

Meralco service voltages

  • Secondary metered: 240 V, 400 V or 460 V
  • Primary metered: 34.5 kV; 13.8 kV in parts of Cavite and Bulacan; 115 kV for subtransmission

Transformers Meralco supplies for vault installation

These are Meralco-supplied units. If you are buying a transformer for your own installation, ask Meralco or the utility serving your site which voltages and protection arrangement it requires.

  • Three-phase padmounted: 34.5 GrdY/20 kV or 13.2 GrdY/7.62 kV primary; secondary 240Y/139 V (75–1000 kVA), 480Y/277 V (500–2000 kVA) or 416Y/240 V (500–1000 kVA)
  • Single-phase deadfront: 34.5 GrdY/20 kV or 13.2 GrdY/7.62 kV primary; secondary 139/277 V or 240/120 V; 167–333 kVA
  • Deadfront primary and less-flammable liquid fill; the three-phase units are completely self-protected with fuses and have a loop sectionalizing switch

Product certification

DTI’s Bureau of Philippine Standards (BPS) runs two mandatory schemes: the PS mark for locally made goods and the Import Commodity Clearance (ICC) for imports. The BPS list of products under mandatory certification covers household appliances, consumer electronics, and lighting and wiring devices such as circuit breakers, fuses, plugs, sockets and cables. Distribution transformers are not on that list.

Tender documents can still ask for type-test and routine-test reports, so check what your buyer or utility requires.

What our published ratings cover

  • Pad-mounted transformers (IEEE/ANSI C57.12, 60 Hz): the published three-phase HV list includes 7.62, 13.2 and 13.8 kV (BIL 95 kV for 7.62 kV, 125 kV for 13.2 and 13.8 kV); ratings 30–3000 kVA including 75, 150, 225, 300, 500, 750, 1000, 1500 and 2000 kVA; published LV options are 240Δ/120 (tap), 480Y/277, 240Δ, 480Δ and 600Y/347 V.
  • 34.5 kV primary, 240Y/139 V and 416Y/240 V secondary, and single-phase 333 kVA: quoted on request. Single-phase pad-mounted sizes published go up to 250 kVA, including 167 kVA.
  • Oil-immersed S11 / S13 loss values on this site are 50 Hz guarantees, and the YBW compact substation catalogue is 50 Hz. 60 Hz units for the Philippines are designed and quoted per order.
  • Dry-type units are published for 6–15 kV; 60 Hz is on request.

Send with your enquiry

  • Distribution utility and site (Meralco or other), and the service voltage at the site
  • Rated power (kVA), HV and LV, vector group, tapping range
  • Pad-mounted, pole-mounted, vault, oil-immersed or dry-type; single-phase or three-phase; 60 Hz
  • Any utility or tender specification, and the test reports it asks for
  • Quantity, delivery port and required date

Request a quotation for Philippines

Send the rated capacity, voltage and quantity — we quote to the grid parameters in Philippines.