English

Home / Oil-Immersed /S13 /1,250 kVA · 10 kV

S13-1250/10 Oil-Immersed Distribution

1,250 kVA · 6 / 6.3 / 10 kV · Dyn11 / Yyn0

S13-1250/10
S13-1250/10Rating plate · guaranteed values
Rated capacity1,250 kVA
HV6 / 6.3 / 10 kV
LV0.4 kV
Vector groupDyn11 / Yyn0
No-load loss970 W
Load loss12,000 W
No-load current0.9 %
Impedance voltage4.5 %
Tapping range±5 % / ±2 × 2.5 %
Oil weight—
Total weight—
Dimensions—

Which grids this rating suits

Low-voltage options and vector groups

Low-voltage options: 0.4 kV. Vector groups: Dyn11 / Yyn0. In IEC notation, Dyn11 means a delta-connected HV winding and a star-connected LV winding with the neutral brought out, the LV phase displaced by 330° (clock position 11) from the HV. Tapping: ±5 % / ±2 × 2.5 %.

Lead time and packing

Lead time is confirmed in each quotation. It depends on quantity, the final specification and any third-party pre-shipment inspection your import scheme requires. Packing and Incoterm are agreed per order — tell us the destination port.

Frequently asked questions

Which countries is the S13 1250 kVA transformer suitable for?

Kazakhstan — HV 6 / 10 kV, LV 380 V, 50 Hz. LV 380 V on request. Uzbekistan — HV 6 / 10 kV, LV 380 V, 50 Hz. LV 380 V on request.

Which low-voltage options and vector groups are available for S13 1250 kVA?

Low-voltage options: 0.4 kV. Vector groups: Dyn11 / Yyn0. In IEC notation, Dyn11 means a delta-connected HV winding and a star-connected LV winding with the neutral brought out, the LV phase displaced by 330° (clock position 11) from the HV. Tapping: ±5 % / ±2 × 2.5 %.

What is the lead time and how is the S13 1250 kVA transformer packed?

Lead time is confirmed in each quotation. It depends on quantity, the final specification and any third-party pre-shipment inspection your import scheme requires. Packing and Incoterm are agreed per order — tell us the destination port.

Related guides